Logo Neptronic
Home TechTime May 2018 HVAC Controls

TechTime is a Neptronic publication aiming to inform you on the best ways to deal with common issues highlighted by our technical support team. Each edition features three new topics and will be posted on neptronic.com.

It's all about organization
Introduction to Controls Wiring Basics Continued from March

This month, we will continue the introduction to controls wiring. For this section, I will be using the following two controllers as examples;

  • TUCB24C6X2 wall mount fan coil controller
  • EVCB14NIT4S unit mount VAV controller

Power Supply Wiring

The power supply must be wired with half-wave class 2 transformers. This allows for the grounding of the neutral. Do not use full-wave transformers to power the controllers and do not ground the neutral of both transformer types.


EVCB Controller
  • Power supply is connected to terminal block #1 (TB1)
  • Pins #1 & #2 are used for the common (-)
  • Pins #3 & #4 are used for the live 24Vac (+)
  • Pins #3 & #4 are used for the live 24Vac (+)
  • Note that the common is grounded

TUCB Controller
  • Has only one terminal block
  • Common (-) is wired to pin #1
  • 24Vac is wired to pin #2

Source/Sink

Sink and Source simply identifies the 24Vac source that will be used to control the equipment.


Using "Source" on an EVCB
  • Jumpers "JP1" and "JP2" are set to "INT"
  • Controller uses its own internal power source

Using "Sink" in an EVCB
  • Jumpers are set to "EXT"
  • Voltage comes from an external power supply
  • Jumper "JP1" is used to set TRIAC Outputs 1 and 2 (TO1 & TO2)
  • Jumper "JP2" is used for TRIAC Outputs 3 and 4 (TO3 & TO2)
  • Can also be used when common switching is required

Some valves may require dry contacts onlt. If this is the case, simply put a jumper between a common and TO1/TO2 pin.

Unit Mount Controller

The EVCB & EFCB series are unit mount controllers. This means that most of the wiring is done locally where the controlled unit is located. When dealing with applications that require a lot of wiring, I suggest using a wall mount controller to cut down on the wire length, cost and labor. It is only a 3 wire connection from the controller to the thermostat which represents the longest run you will have to do.

Temperature Sensor (10kΩ type 3) WIring

A thermistor does not have any polarity meaning that there is no “+” or “-”. It does not matter which wire goes where as long as you have a common and an analog input connected to it.


When two temperature sensors are used but only one common is available, the sensors will have to share the same common. This applies more for a unit mount type controller.


When working with wall mount controllers, your goal is to minimize the quantity of wires required going in the back of the thermostat. Since most of the devices connected to the controller are either in the ceiling or in the unit control panel, it is possible to do just that.


In these examples, there are two temperature sensors connected to the controller. If we follow the logic of minimum two wires per device, this means that we would require four wires for those sensors. If done properly, we could reduce the number of wires to two. To do so, we require a terminal strip installed locally (near the unit) that will hold the common and the 24Vac power from the transformer.

Terminal Strip

Here is an example of a terminal strip application. This type of set-up is more common when using wall mount controllers to limit the number of wires to the thermostat and to secure the wire in place. Depending on the terminal strip, more than one wire can be connected to each screw. Make sure the screws are tight but not too tight as this may cause the wire to break. It is always good to pull the wire gently to make sure it is secured.

Transducers

Transducers require power to operate. Always make sure the power requirement matches the controller and/or the transformer. An example of a transducer would be a 0-10Vdc temperature sensor. Inside the transducer is a thermistor or RTD temperature sensor, which is read by an internal circuit board. The board interprets the signal and simulates a 0-10Vdc based on that temperature reading. The main differences with thermistors are the 24Vac power supply and polarity. In contrary to thermistors, transducer’s polarity must be observed.

Digital (Binary) inputs

There are two types of signals when dealing with binary inputs; dry contacts & wet contacts. Dry contacts do not have any voltage. They simply close the circuit to obtain continuity. Wet contacts, which are more common, require 24Vac or 24Vdc to operate.


Relays can have both a normally opened and a normally closed contact. This is usually the case when dealing with occupancy sensors and changeover switches. Verify the controller’s behavior when contacts are opened or closed. These should be described in the BACnet guide of the product or the specification and installation instructions.

Analog Outputs

Analog inputs require at least two wires to operate; the 0-10Vdc and the common. This is the case when the device has its own power supply such as our duct heaters.


Some analog outputs will require a 24Vac to power up the device such as modulating valves.


ECM fans may require a permission or start/stop command. Even if a 10 volts signal is sent to the fan, it will remain off if the permission is not enabled.

TRIAC Outputs

These types of outputs can be used as binary contacts, floating and pulse. Even though the last two are used in a binary fashion, they are actually simulating a modulating signal. In the floating format, two contacts are used; one to open and one to close. Note that the actuator run time is required to operate properly. The controller uses this configuration to calculate the actuator position.


In the pulse format, the contact is closed based on a time period (most of the time they are based on a 1 second time frame). Depending on the demand, the contact will stay closed or opened for longer periods of time. Note that pulse is only used with heating ramps.

Digital (Binary) Outputs

Unlike the TRIAC outputs, the binary are limited to two states; open and closed. They can be dry contacts or 24Vac (wet contact). The advantage of the binary versus the TRIAC output is that it can be used to close digital inputs.


The TRIAC & binary outputs can handle ON/OFF devices as well as staged devices.


For the last section, I wanted to show an example of External Signal (Sink). A transformer relay does not require power or a 24Vac contact to be activated. It only requires the contact to close in order to pass the 24Vac/Vdc generated by the transformer to power up the relay. When the relay closes, the heater is energized.